ADJUSTIBLE CONSTANT VOLUME HEATING


Units equipped with the optional constant volume heating feature have a change-over thermal element located on the operating mechanism in the neck of the unit. Damper opening adjustment in the heating cycle is provided on the face of the unit under the appearance panel. It is accessed by sliding the appearance panel back exposing the controls. The constant volume heating adjustment sets the damper opening and volume when the unit is in the heating cycle. The adjustability is from a full closed to a full open damper position.

The unit goes into the heating mode when the supply air temperature is 78 degrees or higher. The change over element senses the elevated supply air temperature and opens the damper to the pre-set volume set by the constant volume heating damper adjustment. The unit will switch back to VAV cooling when the supply air temperature drops below 70 degrees Fahrenheit. The change over element sense the lower supply temperature and returns control to the room element.

 