The EFS operates by sensing room
temperature with a solid state thermistor temperature sensor. The signal from
the thermistor over a 1 1/2 degree F. proportional band modulates the diffuser
damper from closed to full open. A sensor in the primary air supply operates
the unit in the cooling mode (Direct acting thermostat) when the supply air
temperature is 65 degrees F. or less and in the
heating mode (reverse acting thermostat) when the supply air temperature is 85
degrees F. or greater. The EFS series diffuser has a solid appearance panel
and is available in an architectural series with a "drop down" architectural
panel that will accept ceiling tile. The appearance and architectural panels
conceal the Electronic set point controls and are easily opened for convenient
access to all of the unit controls. |
The "Electra-Flow Series" (EFS) diffusers were developed to
compliment the (VFS) thermally powered diffusers. The purpose of the diffuser
is to provide a wide range of installation flexibility, accuracy of Electronic
control, and the comfort of individual room zone control. The diffuser uses a
sleeve damper unique to "Vari-Flow" products to provide high levels of
secondary room air induction with a minimum of primary air volume. This is
accomplished by varying the discharge area of the diffuser. As the discharge
area is reduced, the discharge velocity is increased to maintain a constant
level of secondary air induction. This, in conjunction with the horizontal
primary air discharge pattern, prevents "dumping." The efficiency of the air distribution is proven by applying the diffuser to
exposed duct. In this application, the diffuser will maintain a horizontal air
flow pattern over the entire spectrum of air volume from full flow to close
off. The efficient use of primary air energy sustains secondary air movement
to minimize stratification and maintain comfortable levels of room ventilation
with minimum amount of primary air flow. The EFS24 is powered by a unique "thermal motor" that proportionately operates
the damper. The "thermal motor" operates without motor windings, stators,
armatures or bearings. This distinctive power source operates on the simple,
basic principal of thermal expansion when a substance changes state, in this
case from a liquid to a solid. The thermal motor has a proven history of
reliability and long life.
|
Flexibility
Multiple discharge patterns
Suitable for master/slave configurations
Fits modular ceiling systems (Spline,
Plaster, fineline grids)
Simple to relocate with occupancy changes
Suitable for low temperature distribution
systems
Appearance
Economical
Simple to install, simple to service
Self-contained control system
Energy efficient, minimum static pressure
required
|
|